FLW Wet Location

FLW Wet Location

Downloads
IES - Ceiling
IES - Wall

Specifications
Construction: High-quality vandal, corrosion and flame resistant RAL 7035 color polycarbonate (light grey)
Battery: Standard unit utilizes a 4-cell NiCad battery that provides a minimum of 90 minutes of emergency operation
Lamp: The FLW unit utilizes a 24 Watt compact
fluorescent lamp (1800 lumens output)
Less the 3% of lumens lost due to highly efficient reflector and lens design (included)
Reflector: Injection molded, self-extinguishing,
UV stabilized polycarbonate
Vacuum finished to enhance the highly
reflective surface
Supports components including the lamp holder and reflective hood
Diffuser: UV stabilized to provide superior output
and reduce yellowing index
Co-injection process increases strength
and durability
Vandal Resistant Design: Fully enclosed and protected lamp assembly
Vandal resistant flush housing latch clips ensure the protection of the FLW Series
Installation: Surface and recess ceiling or wall mount
Approvals: Listed to UL924 Standard for damp
and wet locations
Self Diagnostics: FLW Series comes standard with self-diagnostic that continually monitors the lamp, battery and circuitry for proper operation
Warranty: Isolite offers a 5-year limited warranty. For further details, refer to General Warranty and Obligations in Isolite manual. Lamps not warranted.

Ordering Information
SeriesLampOperationVoltageSelf DiagnosticsOptions
FLW
24 = 24 Watt Flourescent Lamp
AC = AC Only
EM = Battery Backup
U = Universal 120/277
SD = Self Diagnostics (Standard)
FT = Recessed Housing (T-Bar)
FD = Recessed Housing (Dry Wall)